New Fashion Design for 0.5~800kVA UPS 220/380VAC for Industry and Commercial Field, PC, Computer/It Room, Data Center Power Supply
Our intention would be to fulfill our consumers by offering golden support, great price and high-quality for New Fashion Design for 0.5~800kVA UPS 220/380VAC for Industry and Commercial Field, PC, Computer/It Room, Data Center Power Supply, Our professional technical team will be wholeheartedly at your service. We sincerely welcome you to visit our website and company and send us your inquiry.
Our intention would be to fulfill our consumers by offering golden support, great price and high-quality for China UPS and Online UPS, Our stock have valued 8 million dollar , you can find the competitive parts within short delivery time. Our company is not only your partner in business, but also our company is your assistant in the coming corporation.
Features
Little Hint
1. In the warranty period the machine has a problem, please contact the sales staff, we will be responsible for customer service.
2. Exceed the warranty period, improper operation and man-made damage, we will still give help and support, we will provide spare parts at a cost price.
3. According to the customer’s needs, we can provide unconventional, but the cost may be slightly higher than the traditional machine.
Applications
Data processing center, The host system, Computer servers, Medical, Traffic, Electricity, IT, Industrial and other industries.
Factory Production Line
Packaging
Our intention would be to fulfill our consumers by offering golden support, great price and high-quality for New Fashion Design for 0.5~800kVA UPS 220/380VAC for Industry and Commercial Field, PC, Computer/It Room, Data Center Power Supply, Our professional technical team will be wholeheartedly at your service. We sincerely welcome you to visit our website and company and send us your inquiry.
New Fashion Design for China UPS and Online UPS, Our stock have valued 8 million dollar , you can find the competitive parts within short delivery time. Our company is not only your partner in business, but also our company is your assistant in the coming corporation.
MODEL |
BNT9010S(H)-33* |
BNT9020S(H)-33* |
BNT9030S(H)-33* |
BNT9040S(H)-33* |
BNT9060H-33 |
BNT9080H-33 |
BNT9100H-33 |
BNT9120H-33 |
BNT9160H-33 |
BNT9200H-33 |
|
PHASE |
3-phase in / 3-phase out |
||||||||||
CAPACITY |
10KVA /9KW |
20KVA /18KW |
30KVA/27KW |
40KVA/36KW |
60KVA/54KW |
80KVA/72KW |
100KVA/90KW |
120KVA/108KW |
160KVA/144KW |
200KVA/180KW |
|
PARALLEL CAPABILITY |
up to 3 units in parallel |
up to 2 units in parallel | |||||||||
INPUT | |||||||||||
Nominal Voltage |
3 x 400 VAC (3Ph+N) |
||||||||||
Voltage Range |
190-520 VAC (3-phase) @ 50% load;305-478 VAC (3-phase) @ 100% load |
208-478 VAC (3-phase) @ 70% load;305-478 VAC (3-phase) @ 100% load | |||||||||
Frequency Range |
46~54 Hz or 56~64Hz |
40~70Hz |
|||||||||
Power Factor |
≧ 0.99 @ 100% Load |
||||||||||
OUTPUT | |||||||||||
Output Voltage |
3 x 360*/380/400/415 VAC (3Ph+N) |
3 x 380/400/415 VAC (3Ph+N) |
|||||||||
AC Voltage Regulation (Batt. Mode) |
± 1% |
||||||||||
Frequency Range (Synchronized Range) |
46~54Hz or 56~64Hz |
||||||||||
Frequency Range (Batt. Mode) |
50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz |
||||||||||
Current Crest Ratio |
3:1 (max.) |
||||||||||
Harmonic Distortion |
≤2 % THD (Linear Load); ≤4 % THD (Non-linear Load) |
≤2 % THD (Linear Load); ≤4 % THD (Non-linear Load) | |||||||||
Transfer Time |
Zero |
||||||||||
Inverter to Bypass |
Zero |
||||||||||
Waveform (Batt. Mode) |
Pure Sine wave |
||||||||||
Overload | AC Mode |
100-110% for 10 min, 110-130% for 1 min,>130% for 1 second |
105-110% for 1 hr, 111-125% for 10 min,126-150% for 1 min, >150% for 200ms |
||||||||
Battery Mode |
100-110% for 30 seconds, 110-130% for 10 seconds, |
105-110% for 1 hr, 111-125% for 10 min,126-150% for 1 min, >150% for 200ms |
|||||||||
EFFICIENCY | |||||||||||
AC Mode |
95.50% |
94.00% |
|||||||||
ECO Mode |
97.00% |
98.00% |
|||||||||
Battery Mode |
93.50% |
93.00% |
|||||||||
BATTERY | |||||||||||
Standard Model |
Numbers |
(16+16) pcs x 1 string |
(16+16) pcs x 2 strings |
N/A |
|||||||
Typical Recharge Time |
9 hours recover to 90% capacity |
||||||||||
Charging Current (max.) |
1A/2A/3A/4A (Adjustable) |
||||||||||
Charging Voltage |
+/-218 VDC ± 10% |
||||||||||
Long-run Model | Battery Type |
Depending on the capacity of external batteries |
|||||||||
Numbers |
32~40 pcs (Adjustable) |
||||||||||
Charging Current (max.) |
1A/2A/3A/4A (Adjustable)Parallelable up to 3 charger boards to reach 12A maximum |
2A/4A/6A/8A (Adjustable) Parallelable up to 3 sets of dual charger boards to reach 24A maximum |
24A |
32A |
40A |
48A |
|||||
Charging Voltage |
+/- 13.65V x N (N=16~20) |
+/- 13.7V x N (N = 16~20) |
|||||||||
INDICATORS | |||||||||||
LCD Display |
UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions |
10” Touch Type color LCD |
|||||||||
PHYSICAL | |||||||||||
Standard Model | Dimension, D x W x H (mm) |
627 x 250 x 750 |
815 x 300 x 1000 |
N/A |
|||||||
Net Weight (kg) |
129 |
144 |
225 |
250 |
|||||||
Long-run Model | Dimension, D x W x H (mm) |
627 x 250 x 750 |
815 x 300 x 1000 |
790 x 360 x 1010 |
940 x 567 x 1015 |
1040 x 567 x 1452 |
|||||
Net Weight (kg) |
33 |
48 |
60 |
61 |
108 |
113 |
199 |
234 |
306 |
340 |
|
ENVIRONMENT | |||||||||||
Operation Temperture |
0-40°C |
||||||||||
Operation Humidity |
< 95% and non-condersing |
||||||||||
Noise Level |
Less than55dB@ 1 Meter |
Less than 60dB@1 Meter |
Less than 70dB @ 1 Meter |
Less than 75dB@1 Meter |
Less than 70dB @ 1 Meter |
Less than 73dB @ 1 Meter |
|||||
MANAGEMENT | |||||||||||
Smart RS-232 / USB |
Supports Windows2 2000/2003/XP/Vista/2008, Windows2 7/8/10, Linux and MAC |
||||||||||
Optional SNMP |
Power management from SNMP manager and web browser |